B VARD 560/8/4 F 400

B VARD 560/8/4 F 400

HIGH TEMPERATURE MIXED-FLOW FAN 3-PH, 400°C/120 MIN. 2-speed, Dahlander winding 710/1440 MIN-1, 0,75/3,6 KW

Ref.-No. 02413

Features

High pressure smoke extract fan, temperature class F 400 to DIN 12101 part 3. Cylindrical pre-galvanised sheet-steel casing with a rolled flange at both ends Dimensions and flange fixing holes to DIN 24155, page 2. With guide vanes for improved performance. Mixed flow impeller with 8 spatially curved blades from galvanised steel. Dynamically balanced to class G 6.3 VDI 20060 and DIN ISO 1940. Totally enclosed, 3-phase squirrel cage motor, 2-speed (pole switching with Dahlander windings). Maintenance free with low-noise sealed for life ball bearings.

Technical Data

General Information
Ref.-No.:02413
Type:B VARD 560/8/4 F 400
Flow rate free-blowing:14970 m³/h
RPM:690 / 1410 min-1
Number of poles:8 / 4
Voltage:400 / 400 V , 3 ph , 50 Hz
Rated current (FLC) uncontrolled:2.41 / 6 A
Nominal power:0.7 / 2.8 kW
Max. air flow temperature:40 °C
Temperature class:F400
IP protection category:55
Insulation class:H
PRODUCT_DETAILPAGE_wheel_diameter:560 mm
Weight:106 kg
Wiring diagram no.:777