B-IVRD 560/8/4 F 300

B-IVRD 560/8/4 F 300

Centrifugal smoke extraction jet fan 3-ph. 400 V 50 Hz 300°C/120 MIN. pole switching

Ref.-No. 04160

Features

High-quality, powerful jet fans with optimal dimensions for smallest space requirements. Suitable for supply and extract ventilation or smoke extraction in car parks. Temperature range 300 °C/120 min. (in smoke extraction operation) or 60 °C in permanent operation.

Technical Data

General Information
Ref.-No.:04160
Type:B-IVRD 560/8/4 F 300
Flow rate free-blowing:8900 m³/h
RPM:700 / 1420 min-1
Number of poles:8 / 4
Voltage:400 V , 3 ph , 50 Hz
Rated current (FLC) uncontrolled:2.02 / 5.04 A
Nominal power:0.5 / 2.2 kW
Max. air flow temperature:60 °C
Temperature class:F300
Sound insulated:
IP protection category:55
Insulation class:H
PRODUCT_DETAILPAGE_wheel_diameter:560 mm
Weight:72 kg
Thrust:19 / 75
Wiring diagram no.:777