KWL EC 2000 D PRO

KWL EC 2000 D PRO

Ceiling unit with heat recovery EC-fans automatic bypass, graphic display

Ref.-No. 04175

Features

Central ventilation unit for ceiling installation with heat recovery , EC-fans, electric pre-heater battery, automatic bypass, graphic display . Ventilation unit tested according to passive-house standards with efficiency over 80%. With larger surface cross counterflow heat exchanger including automatic bypass with 100% heat exchanger covering and maintenance-free EC-fans. User-friendly operation over elf-describing graphic elements with plain text directly at the touchscreen, incl. weekly program, calibration menu, code-protected service menu, etc. Choice between constant air flow volume or constant pressure regulation. Integrated electric pre-heater for extremely cold seasons. In order to achieve a constant supply air temperature an external warm water heater battery can be controlled over the unit control by means of the optionally available hydraulic unit WHSH 1100 24V (0-10V).Control of external exhaust and intake air shutters. Via an external switch, the unit can be set in standby mode. In addition, a contact for the fire alarm and additional contact for external control is available. Demand oriented ventilation using CO2- or humidity sensor.

Technical Data

General Information
Ref.-No.:04175
Type:KWL EC 2000 D PRO
Flow rate free-blowing:2400 m³/h
Speed control:ELECTRIC
Voltage:400 V , 3 ph , 50 Hz
Rated current (FLC) uncontrolled:16 A
Max. air flow temperature:40 °C
IP protection category:20
Weight:265 kg
Unit design:universal
Installation position:ceiling
Heat exchanger:plate heat exchanger
ErP-ηt::78.9 %
Wiring diagram no.:1370