AIR1 XH 5500
AIR1 XH 5500
Ventilation unit with heat recovery Cross-counterflow heat exchanger Standing version, electric pre-heater


Ref.-No. 04340
Features
Compact ventilation unit with heat recovery for floor-standing installation indoors or outdoor installation, including control system, fully wired. Universal installation with outdoor air connection on the left or right possible. Built-in electric preheating register to protect the heat exchanger from freezing at very low outdoor air temperatures. For increased comfort temperature requirements, an electric or hot water reheating coil can be installed in the unit housing as an option. Housing: Consisting of robust and stable aluminium frame profiles, thermally optimised to minimise thermal bridges. Double-walled panels made of aluzinc sheet metal, insulated on all sides with 50 mm mineral wool for optimum heat and sound insulation, coated on the outside with a corrosion-resistant finish (class C4) (RAL 7047), galvanised on the inside. Enclosure classes according to DIN EN 1886: T2/TB2/D2, generous inspection openings on both sides of the unit for easy access to all unit components and optimum cleaning and maintenance options. The unit is delivered in segments for easy transport/installation at the installation site. Condensate connection option at the bottom of the unit: 1 x exhaust air side, 1 x supply air side, DN 32 mm. Stainless steel condensate tray with integrated slope. Eurovent-certified cross-counterflow plate heat exchanger made of aluminium with high thermal efficiency of up to 90% in accordance with EN 308. The heat exchanger has a high internal tightness and is therefore particularly suitable for applications where there is a risk of odour transfer. The heat exchanger module is equipped as standard with an automatic bypass flap mechanism with complete coverage of the heat exchanger for free cooling (night cooling) and cold recovery in summer.Fans: 2 direct-drive EC motors, class IE4 with very low SFP values, dynamically balanced and vibration-damped in the unit. Steplessly controllable via 0-10V signal. Plug connections on all electrical components to simplify maintenance work. Filters: Two large-area, pressure loss-optimised cassette filters are installed as standard (outdoor air ePM155% (F7) and exhaust air ePM10 50% (M5)). Use up to filter class ePM1 80% (F9) in the outside air and ePM1 55% (F7) in the exhaust air is optionally possible. In addition, a pre-filter of class ePM 10 50% (M5) can be used in the outside air directly in the unit. The filters are monitored by means of dynamic, volume flow-dependent pressure monitoring. Control: The ventilation unit is delivered ready for operation with a versatile control system. The control system is easy to maintain, located in a connection box on the side of the unit, factory-wired and function-tested. Two control elements (ECO and Touch) are available (required accessories). Control functions: Ventilation modes: constant volume CAV, constant pressure VAV (accessories required), constant speed CRPM in % or via weekly program. Automatic ventilation mode/ventilation on demand (VOD) via humidity, CO2 or VOC sensors. Up to 18 sensors can be connected per ventilation unit. Free cooling, active cooling via cooling register (cold water or DX). Temperature control, e.g. constant supply air, supply air controlled by outside temperature, room supply air cascade, etc. possible. Digital inputs for fire alarm and external switch (on/off). Digital output for collective fault signal. External fan control via two analogue 0-10V inputs (supply air and exhaust air fan separate). Connection to the building management system via BACnet IP or Modbus TCP possible. Commissioning wizard for quick and easy commissioning of the unit and the appropriate accessories.Additional data and accessories
Technical Data
General Information
Ref.-No.: | 04340 |
---|---|
Type: | AIR1 XH 5500 |
Flow rate free-blowing: | 7200 m³/h |
Voltage: | 400 V , 50 Hz |
Rated current (FLC) uncontrolled: | 33.7 A |
Max. air flow temperature: | 50 °C |
IP protection category: | 31 |
Weight: | 873,00 kg |
Unit design: | universal |
Installation position: | floor |
Heat exchanger: | plate heat exchanger |
ErP-ηt:: | 80,8 % |
P-qnom (nominal air flow): | 1,5 m³/s |
Wiring diagram no.: | 1331 |
Quicklinks
Additional data and accessories
Oops, hier ist die Luft raus...
Die Seite wurde nicht gefunden. Mögliche Ursachen:
- Die gewünschte Seite existiert nicht bzw. nicht mehr.
- Bei der Eingabe der URL gab es einen Tippfehler.
- Es wurde ein veraltetes Lesezeichen oder ein veralteter Link verwendet.
Das können Sie tun:
Hauptmenü (Infoleiste oben)

Helios ELS App – ELS NFC
Volumenströme, Nachlaufzeiten, Sensoreinstellungen und mehr: Ihren ELS NFC programmieren Sie in Sekundenschnelle per App.

Helios FDR App – Feuchte-Differenz-Regelung
Das Helios System zur Feuchte-Differenz-Regelung können Sie ganz einfach und zuverlässig mit einer App auf dem Smartphone oder einem Tablet einstellen.
Helios locations in Europe

Helios Ventilatoren GmbH + Co KG
Lupfenstraße 8
78056 Villingen-Schwenningen - DE
Phone: +49 (0) 7720 / 606-0
Fax: +49 (0) 7720 / 606-166
E-Mail:

Helios Ventilatoren Ges. mbH
Siemensstrasse 15
6063 Rum/Innsbruck
Phone: +43 (0) 512/26 59 88
Fax: +43 (0) 512/26 59 88 – 85
E-Mail:

Helios Ventilatoren AG
Tannstrasse 4
8112 Otelfingen
Phone: +41 (0)44 735 36 36
Fax: +41 (0)44 735 36 37
E-Mail:

Helios Ventilation Systems
5 Crown Gate, Wyncolls
RoadSeveralls Industrial Park
Colchester, Essex CO4 9HZ
Phone: +44 (0)1206 228 500
Fax: +44 (0)1206 228 501
E-Mail: