B AVD 900/4 5,5 kW F300

B AVD 900/4 5,5 kW F300

Smoke exhaust axial fan 3-PH, 300°C/120 MIN. 1450 RPM, 5,50 KW

Ref.-No. 02362

Features

High pressure smoke extract fan, temperature class F 300 to DIN 12101 part 3. Short cylindrical casing in galvanised sheet steel covering impeller (motor protrudes at rear) with two flanges on both ends. Dimensions and flange fixing holes to DIN 24155. Impeller with 9 blades from aluminium, high efficiency. Totally enclosed, 3-phase squirrel cage motor. Maintenance-free with low-noise sealed for life ball bearings.

Technical Data

General Information
Ref.-No.:02362
Type:B AVD 900/4 5,5 kW F300
Flow rate free-blowing:34560 m³/h
RPM:1460 min-1
Number of poles:4
Voltage:400 / 690 V , 3 ph , 50 Hz
Rated current (FLC) uncontrolled:10.4 / 6.03 A
Max. air flow temperature:40 °C
Temperature class:F300
IP protection category:54
Insulation class:H
PRODUCT_DETAILPAGE_wheel_diameter:900 mm
Weight:145 kg
Wiring diagram no.:776