B AVD 1000/8/4 6,5/28 kW F300

B AVD 1000/8/4 6,5/28 kW F300

Smoke exhaust axial fan FAN 3-PH, 300°C/120 MIN., 2-speed, Dahlander winding 740/1480 RPM, 6,00/30,00 KW

Ref.-No. 02380

Features

High pressure smoke extract fan, temperature class F 300 to DIN 12101 part 3. Short cylindrical casing in galvanised sheet steel covering impeller (motor protrudes at rear) with two flanges on both ends. Dimensions and flange fixing holes to DIN 24155. Impeller with 9 blades from aluminium, high efficiency. Totally enclosed, 3-phase squirrel cage motor, 2-speed (pole switching with Dahlander windings). Maintenance free with low-noise sealed for life ball bearings.

Technical Data

General Information
Ref.-No.:02380
Type:B AVD 1000/8/4 6,5/28 kW F300
Flow rate free-blowing:88240 m³/h
RPM:735 / 1480 min-1
Number of poles:8 / 4
Voltage:400 / 400 V , 3 ph , 50 Hz
Rated current (FLC) uncontrolled:18 / 52 A
Nominal power:6.5 / 28 kW
Max. air flow temperature:40 °C
Temperature class:F300
IP protection category:54
Insulation class:H
PRODUCT_DETAILPAGE_wheel_diameter:1000 mm
Weight:350 kg
Wiring diagram no.:777